Industrial Ground Source Heat Pump

Model NO.: MPHG
Compressor Type: 5:6 Asymmetric Semi-Closed Twin Screw
Chilled/Hot Water Flow: 76.5m3/h to 182m3/h
Ground Water Source: 43.5m3/h to 103m3/h
Energy Regulation Range: 0 - 25% - 50% - 75% - 100%
Power Supply: 220V to 575V(Customized)
Guarantee Period: 15 Months
Life-Time: More Than 5 Years
Trademark: MAIPT
Transport Package: Wooden Case
Specification: 3225*900*1960mm
Origin: China
HS Code: 8418699090
Model NO.: MPHG
Compressor Type: 5:6 Asymmetric Semi-Closed Twin Screw
Chilled/Hot Water Flow: 76.5m3/h to 182m3/h
Ground Water Source: 43.5m3/h to 103m3/h
Energy Regulation Range: 0 - 25% - 50% - 75% - 100%
Power Supply: 220V to 575V(Customized)
Guarantee Period: 15 Months
Life-Time: More Than 5 Years
Trademark: MAIPT
Transport Package: Wooden Case
Specification: 3225*900*1960mm
Origin: China
HS Code: 8418699090
Industrial Ground Source Heat Pump
 
 BRIEF DESCRIPTION WWW.MAIPT.LTD/
MPHG~ series Screw Type Ground Source Heat Pump Unit is the latest developed product which has a wide cooling capacity range from 105KW to 2110KW. This series unit adopt: 5:6 Asymmetric Semi-closed Screw Compressor, High-efficiency Shell & Tube Dry Type Evaporator, High-efficiency Shell & Tube Type Condenser etc. By means of decades manufacturing experience, we make the whole chiller unit with compact appearance, reasonable layout and convenient for using &maintenance etc. characteristics.

The cooling medium for this series chiller unit could be water, glycol solution or salt solution, supply chilled water through refrigerating cycle for air-conditioning or other industrial equipments.
Industrial Ground Source Heat Pump
 FEATURES / FUNCTIONS / SAFETY PROTECTIONS WWW.MAIPT.LTD/
 
 FEATURES * OPTIONAL FUNCTIONS
- Adopt the well-known brand compressors * Special brine evaporator
- Control mode: PLC Full Automatic Control * RS485 remote control function
- Copper tube is welded with oxygen free method * Total heat recovery or part heat recovery
- 5:6 Asymmetric Semi-closed Screw Compressor * Customizable painting colour or OEM&ODM
- SUS integrated pipelines for less pipe resistance * Complete refrigeration system scheme design
- Multi-steps energy regulation or stepless regulation * Explosion-proof electric cabinet or components
- System pressure & Functional test before shipping * Customizable power supply and cooling capacity
- Highly efficient evaporator and condenser (30% energy saving) * Different refrigerants are available, R22, R134a, R407C etc
- Electrical devices supplied from OMRON, C8, LG, SCHNEIDER * Different outlet water Temp.(10°C,7°C,0°C,-5°C to -35°C) is available
  SAFETY PROTECTIONS                                                   
- Overheating protection of compressor's motor - Phase protection of power supply
- Discontinuous flow protection of cooling/chilled water - Anti-freezing protection of chilled water
- Over-voltage & under-voltage protection of power supply - Three-phase Unbalance protection of power supply
- Protection for exhaust temperature of compressor is too high - Protection for low pressure of refrigerant is too low
- Protection for outlet temperature of chilled water is too high  - Protection for high pressure of refrigerant is too high
 
 TECHNICAL SPECIFICATION WWW.MAIPT.LTD/

Specification Table for MPHG Series
Model MPHG-
445.1G 530.1G 560.1G 610.1G 660.1G 690.1G 790.1G 875.1G 945.1G 1055.1G
Refrigeration
Condition
Cooling Capacity KW 445 530 560 610 660 690 790 875 945 1055
Input Power KW 78.9 91.6 96.7 105 113 116 137 152 161 178
Rated Current A 137 159 167 181 195 201 237 263 279 307
Heating
Condition
Heating Capacity KW 419 498 525 575 622 645 746 827 890 992
Input Power KW 104 120 127 137 148 153 179 199 211 233
Rated Current A 179 208 219 238 256 264 310 344 366 403
Heating
Condition
Heating Capacity KW 302 358 378 414 448 460 537 596 641 714
Input Power KW 94.9 110 116 126 136 141 165 183 194 214
Rated Current A 164 191 201 218 235 244 285 316 335 370
Water Flow Chilled/Hot Water m3/hr 76.5 91.2 96.3 105 114 119 136 151 163 182
Ground Water Source m3/hr 43.5 51.8 54.8 59.7 64.5 67.5 77.3 85.6 92.4 103
Pressure Drop Chilled/Hot Water Kpa 57 57 57 61 61 62 62 63 65 67
Ground Water Source Kpa 41 42 44 46 47 47 48 48 50