Capacitor test selection scheme

Moisture (mg/L)

Cycle Claim

66–110kV ≤35

220kV ≤25

330–500kV ≤15

During operation, it is recommended to take the oil temperature into consideration. Sampling should be performed when the top oil temperature is above 50°C, and testing should follow GB7600 or GB7601 standards.

Breakdown Voltage (kV)

Cycle Claim

Below 15kV ≥25

15–35kV ≥30

66–220kV ≥35

330kV ≥45

500kV ≥50

Testing should be conducted according to GB/T 507 and DL/T 429.9 standards.

Tgδ (90°C) (%)

Cycle Claim

300kV and below ≤4

500kV ≤2

The test should be performed in accordance with GB5654.

AC Voltage Withstand Test of Capacitive Voltage Divider of Coupling Capacitor and Capacitive Voltage Transformer

Cycle Claim

When necessary

The test voltage should be set at 75% of the factory test voltage.